Water Cooled Capacitor Data Sheet
Technical Specification
| Rated Output: | Up to 7000 kVAr (higher powers on request) |
| Maximum Outlet Water Temperature: | 40 °C |
| Minimum Flow Rate: | 4.5 litres/minute |
| Capacitance Tolerance: | -5 / +10% |
| Working Voltage (Un): | Up to 3000V AC |
| Working Frequency: | 50Hz - 10kHz (other frequencies available on request) |
| Impregnation Fluid: | Biodegradable, non-PCB |
| Installation: | Indoor, suitable for vertical or horizontal mounting |
| Permitted Overvoltage: | 1.05 x Un for up to 1 hr/day |
| Permitted Overcurrent: | 1.35 x In, including harmonics but excluding transients |
| Switching Overvoltage: | ≤2 x Ö2 x Un |
| Max. Peak Voltage: | 1.65 x Un (including harmonics) |
| Max Torque on M14 nuts: | 10 N-m |
| Dielectric Losses (tan d): | <0.15 W/kVAr |
| Test Voltage between Terminals: | 2.15 x Un AC, 10 secs |
| Test Voltage Terminals and Case: | According to IEC 871-1/2 and TS Standards |
| Fuses: | Not fitted, available on request |
| Discharge Resistors: | Not fitted, available on request |
| Bushings: | Steatite or Wet process Porcelain |
| Altitude: | 2000 metres above sea level |
| Reference Standards: | IEC 110-1/2, VDE0560-0, TS3558 |
| Factory Quality Assurance Standard: | ISO 9001 |